Custom exhaust attenuation for rooftop equipment adjacent to residential buildings
The project focused the treatment on the dominant rooftop discharge path and used removable internal splitters so the attenuation system could be inspected and serviced over the life of the building.
Project Profile
|
Location |
Nanjing, China |
|
Industry |
Hotel and commercial property |
|
Primary noise sources |
Eight rooftop cooling tower units; four units operating simultaneously created the main impact at nearby residences |
|
Baseline condition |
At 1 m outside the nearest residential windows: up to 60.9 dB(A) by day and 59.7 dB(A) at night |
|
Applicable standard or target |
Project target at the residential windows: daytime ≤ 58 dB(A), nighttime ≤ 48 dB(A) |


Project Challenge
The cooling towers were installed on a constrained roof beside occupied residential buildings. The solution had to attenuate the discharge noise while maintaining the airflow and pressure conditions needed for reliable cooling tower operation.
Engineered Solution
- Installed a custom rooftop exhaust attenuator with a total height of 2.6 m, comprising a 1.2 m air-transition section and a 1.4 m attenuation section.
- Added metal sound-absorbing and sound-insulating outer panels around the attenuator to limit leakage and sound diffraction.
- Used sliding removable acoustic splitters, 100 mm thick with approximately 130 mm spacing, designed for ≥ 15 dB attenuation.
- Closed the lower gap between the attenuator and cooling tower with damping acoustic panels to prevent low-level leakage.
- Included an access hatch for routine maintenance.
Performance Targets And Results
|
Metric |
Target or value |
Project interpretation |
|
Measured design attenuation |
19.8 dB theoretical attenuation |
Above the 15 dB design target |
|
Residential noise target |
Daytime ≤ 58 dB(A); nighttime ≤ 48 dB(A) |
Project target at 1 m outside windows |
|
Air performance |
Required airflow and pressure loss maintained |
Cooling tower operation preserved |