Rooftop Cooling Tower Noise Control at a Hotel Complex

Sep 22, 2026 Leave a message

Custom exhaust attenuation for rooftop equipment adjacent to residential buildings

The project focused the treatment on the dominant rooftop discharge path and used removable internal splitters so the attenuation system could be inspected and serviced over the life of the building.

 

Project Profile

 

Location

Nanjing, China

Industry

Hotel and commercial property

Primary noise sources

Eight rooftop cooling tower units; four units operating simultaneously created the main impact at nearby residences

Baseline condition

At 1 m outside the nearest residential windows: up to 60.9 dB(A) by day and 59.7 dB(A) at night

Applicable standard or target

Project target at the residential windows: daytime ≤ 58 dB(A), nighttime ≤ 48 dB(A)

image001
Before Treatment
image003
After Treatment

Project Challenge

 

The cooling towers were installed on a constrained roof beside occupied residential buildings. The solution had to attenuate the discharge noise while maintaining the airflow and pressure conditions needed for reliable cooling tower operation.

 

Engineered Solution

 

  • Installed a custom rooftop exhaust attenuator with a total height of 2.6 m, comprising a 1.2 m air-transition section and a 1.4 m attenuation section.
  • Added metal sound-absorbing and sound-insulating outer panels around the attenuator to limit leakage and sound diffraction.
  • Used sliding removable acoustic splitters, 100 mm thick with approximately 130 mm spacing, designed for ≥ 15 dB attenuation.
  • Closed the lower gap between the attenuator and cooling tower with damping acoustic panels to prevent low-level leakage.
  • Included an access hatch for routine maintenance.

 

Performance Targets And Results

 

Metric

Target or value

Project interpretation

Measured design attenuation

19.8 dB theoretical attenuation

Above the 15 dB design target

Residential noise target

Daytime ≤ 58 dB(A); nighttime ≤ 48 dB(A)

Project target at 1 m outside windows

Air performance

Required airflow and pressure loss maintained

Cooling tower operation preserved

 