High-level L-shaped and U-shaped acoustic barriers for a large cooling tower group
The barrier geometry was tailored to both the ground-level sound path and the elevated exhaust openings, allowing a large cooling tower installation to be treated without enclosing the equipment completely.
Project Profile
|
Location |
Shandong, China |
|
Industry |
Biopharmaceutical manufacturing |
|
Primary noise sources |
Three large induced-draft cooling towers at the northern site boundary |
|
Baseline condition |
Boundary noise of 68-71 dB(A) by day and 59-62 dB(A) at night; approximately 86 dB(A) at the cooling tower air inlets |
|
Applicable standard or target |
GB 12348-2008 Class III area: daytime ≤ 65 dB(A), nighttime ≤ 55 dB(A) |


Project Challenge
The cooling towers were large and open to the boundary, so the design had to reduce line-of-sight noise while preserving the airflow required for heat rejection and keeping access available for maintenance.
Engineered Solution
- Built an L-shaped metal acoustic barrier approximately 11 m high and 58 m long at ground level.
- Added U-shaped barriers around the upper exhaust openings, extending 1.6 m above the discharge level.
- Used a multilayer panel consisting of 0.8 mm profiled steel sheet, 1.0 mm damping layer, 100 mm 100K rock wool and 0.6 mm perforated facing.
- Designed the acoustic panel system for ≥ 25 dB sound insulation.
- Provided an acoustic access door for inspection and maintenance.
Performance Targets And Results
|
Metric |
Target or value |
Project interpretation |
|
Boundary noise |
Daytime ≤ 62 dB(A); nighttime ≤ 53 dB(A) |
Target performance after treatment |
|
Noise reduction |
Approximately 15-18 dB(A) |
Design performance range |
|
Operations |
Normal ventilation and heat dissipation |
Production unaffected |