Projects

Cooling Tower Boundary Noise Control for a Biopharmaceutical Facility

Sep 22, 2026 Leave a message

High-level L-shaped and U-shaped acoustic barriers for a large cooling tower group

The barrier geometry was tailored to both the ground-level sound path and the elevated exhaust openings, allowing a large cooling tower installation to be treated without enclosing the equipment completely.

 

Project Profile

 

Location

Shandong, China

Industry

Biopharmaceutical manufacturing

Primary noise sources

Three large induced-draft cooling towers at the northern site boundary

Baseline condition

Boundary noise of 68-71 dB(A) by day and 59-62 dB(A) at night; approximately 86 dB(A) at the cooling tower air inlets

Applicable standard or target

GB 12348-2008 Class III area: daytime ≤ 65 dB(A), nighttime ≤ 55 dB(A)

image001
Before Treatment
image003
After Treatment

Project Challenge

 

The cooling towers were large and open to the boundary, so the design had to reduce line-of-sight noise while preserving the airflow required for heat rejection and keeping access available for maintenance.

 

Engineered Solution

 

  • Built an L-shaped metal acoustic barrier approximately 11 m high and 58 m long at ground level.
  • Added U-shaped barriers around the upper exhaust openings, extending 1.6 m above the discharge level.
  • Used a multilayer panel consisting of 0.8 mm profiled steel sheet, 1.0 mm damping layer, 100 mm 100K rock wool and 0.6 mm perforated facing.
  • Designed the acoustic panel system for ≥ 25 dB sound insulation.
  • Provided an acoustic access door for inspection and maintenance.

 

Performance Targets And Results

 

Metric

Target or value

Project interpretation

Boundary noise

Daytime ≤ 62 dB(A); nighttime ≤ 53 dB(A)

Target performance after treatment

Noise reduction

Approximately 15-18 dB(A)

Design performance range

Operations

Normal ventilation and heat dissipation

Production unaffected

 

Send Inquiry