A layered solution combining acoustic enclosures, exhaust silencers and a freestanding barrier
The project used a system-level approach rather than treating one noise source in isolation. Enclosure, exhaust silencing and barrier geometry were coordinated around the actual equipment layout and maintenance requirements.
Project Profile
|
Location |
Zhejiang, China |
|
Industry |
Solar and renewable energy manufacturing |
|
Primary noise sources |
Process equipment, hot exhaust fans, cooling towers and HVAC equipment |
|
Baseline condition |
Boundary noise up to 89 dB(A) |
|
Applicable standard or target |
GB 12348-2008 Class III area: daytime ≤ 65 dB(A), nighttime ≤ 55 dB(A) |


Project Challenge
Several equipment groups were distributed across different elevations near the southern site boundary. The treatment therefore had to control direct radiation, exhaust noise and elevated noise paths without restricting ventilation or routine inspection.
Engineered Solution
- Enclosed the second-floor equipment zone with composite sound-absorbing and sound-insulating modules rated at ≥ 30 dB weighted sound insulation.
- Added an upward-facing exhaust silencer system for the hot exhaust fans, with a design attenuation of ≥ 20 dB.
- Installed a 6 m high single-sided acoustic barrier along the boundary-facing side of the first-floor platform.
- Applied additional absorption and localized enclosure treatment around the top-level equipment area to reduce upward-radiated noise.
- Integrated acoustic doors, observation windows and maintenance access routes into the enclosure design.
Performance Targets And Results
|
Metric |
Target or value |
Project interpretation |
|
Boundary noise target |
Daytime ≤ 65 dB(A); nighttime ≤ 55 dB(A) |
Designed for Class III boundary compliance |
|
Overall noise reduction |
≥ 24 dB(A) |
Target performance |
|
Operations |
Ventilation and heat dissipation maintained |
Production process not interrupted |