Coordinated enclosure and silencer design for cooling towers, pumps and exhaust equipment
The design treated the rooftop as one acoustic system, while keeping separate airflow paths for each equipment group. This avoided transferring the noise problem from one opening to another.
Project Profile
|
Location |
Nanjing, China |
|
Industry |
Automotive thermal management manufacturing |
|
Primary noise sources |
Rooftop cooling towers, kitchen exhaust units, pumps and outdoor HVAC equipment |
|
Baseline condition |
Approximately 80 dB(A) at the cooling tower air-inlet side; sensitive receptors exceeded the Class I environmental noise limit |
|
Applicable standard or target |
GB 3096-2008 Class I area: daytime ≤ 55 dB(A), nighttime ≤ 45 dB(A) |


Project Challenge
Different equipment types produced different noise paths on the same rooftop. A single generic enclosure would have restricted airflow, so each source required a coordinated treatment for its acoustic and thermal behavior.
Engineered Solution
- Installed separate composite acoustic enclosures around two cooling towers, with ≥ 30 dB weighted sound insulation.
- Added upward exhaust silencers at the cooling tower discharge openings, designed for ≥ 15 dB attenuation.
- Installed 600 mm deep intake silencers on the enclosure air-inlet side, designed for ≥ 20 dB attenuation.
- Applied equipment-specific enclosure and silencer combinations to the kitchen exhaust units and pumps.
- Included acoustic access doors rated at ≥ 25 dB and an anti-short-circuit airflow arrangement to prevent hot-air recirculation.
Performance Targets And Results
|
Metric |
Target or value |
Project interpretation |
|
Sensitive-point target |
Daytime ≤ 55 dB(A); nighttime ≤ 45 dB(A) |
Designed for Class I compliance |
|
Overall noise reduction |
Approximately 25-30 dB(A) |
Target performance range |
|
Operations |
Ventilation, heat dissipation and equipment functions maintained |
Normal use preserved |