Chimney-style silencers, acoustic windows and a barrier system for a sensitive building facade
This case demonstrates why industrial noise control often requires treatment of the whole transmission path. Silencers alone would not have addressed the facade leakage through windows and the curtain-wall zone.
Project Profile
|
Location |
Nanjing, China |
|
Industry |
Electronics research and manufacturing |
|
Primary noise sources |
Multiple fans serving a ground-floor research and office building |
|
Baseline condition |
Fan-zone noise up to 110 dB(A); approximately 74 dB(A) near the road with the fan-room windows closed |
|
Applicable standard or target |
GB 22337-2008 Class II area: daytime ≤ 60 dB(A); equipment not operated at night |


Project Challenge
The building facade contained several weak acoustic points, including fan outlets, windows and the curtain-wall area. The solution had to reinforce these points without blocking the existing ventilation route or future facade maintenance.
Engineered Solution
- Installed one composite chimney-style exhaust silencer at each fan outlet, connected to the modified ductwork and designed for ≥ 20 dB attenuation.
- Added silenced outdoor duct sections with downward-facing discharge and strengthened duct-wall insulation, providing an additional design attenuation of ≥ 5 dB.
- Replaced existing windows with custom acoustic windows to remove a major leakage path.
- Installed an acoustic barrier beside the glass curtain wall using a damping sound-absorbing and sound-insulating system rated at ≥ 30 dB, while reserving clearance for future glass replacement.
- Provided a 0.8 m x 2 m acoustic door rated at ≥ 30 dB for routine inspection.
Performance Targets And Results
|
Metric |
Target or value |
Project interpretation |
|
Roadside noise target |
Daytime ≤ 60 dB(A) |
Designed for Class II compliance |
|
Exhaust silencer performance |
≥ 20 dB attenuation |
Design target |
|
Facade performance |
Weak acoustic points reinforced |
Windows, ductwork and curtain-wall area treated |