Rooftop Kitchen Exhaust Noise Control for a Commercial Retail Complex

Sep 22, 2026 Leave a message

Acoustic enclosures and upward-discharge silencers for rooftop food-service equipment

The enclosure and exhaust silencer were designed as one system. This kept the discharge path open and upward while controlling leakage through the enclosure walls, doors and service interfaces.

 

Project Profile

 

Location

Nanjing, China

Industry

Commercial retail and food service

Primary noise sources

Four rooftop kitchen exhaust units

Baseline condition

Approximately 96 dB(A) beside the operating exhaust fans; up to 64 dB(A) inside tenant areas

Applicable standard or target

GB 22337-2008 Class II area for social-life environmental noise

image001
Before Treatment
image003
After Treatment

Project Challenge

 

The exhaust equipment was directly above occupied tenant areas. The noise-control system had to reduce structure-borne and airborne noise while keeping smoke exhaust performance and maintenance access available.

 

Engineered Solution

 

  • Installed three composite acoustic enclosures around adjacent equipment groups, using a structure rated at ≥ 30 dB sound insulation.
  • Added impedance-composite exhaust silencers with upward discharge, rain caps and directional exhaust ducts, designed for ≥ 20 dB attenuation.
  • Provided acoustic access doors rated at ≥ 30 dB.
  • Removed part of the original vertical ductwork to create the installation space required for the new silencing system.
  • Used a multilayer enclosure consisting of aluminum sheet, damping acoustic board, 100 mm 100K acoustic wool, non-alkali glass cloth and perforated aluminum facing.

 

Performance Targets And Results

 

Metric

Target or value

Project interpretation

Tenant-area noise

Reduced to meet the Class II requirement

Target performance

Enclosure insertion loss

≥ 25 dB(A)

Design target

Exhaust performance

Airflow and pressure maintained

Smoke extraction unaffected

 