Oct 05, 2026 Leave a message

At a hotel in Nanjing, eight rooftop cooling towers faced a residential building. The design problem was specific: reduce the noise reaching the homes opposite while preserving the cooling conditions required by the hotel.

 

The project records show that noise affected the neighboring building with four towers operating. A maximum nighttime reading of 59.7 dB(A) was recorded one meter outside a window at the nearest residential building. That location gave the design a clear point of reference.

 

The proposed treatment addressed several sound paths. Custom silencers were specified at the tower outlets, with acoustic panels around the perimeter. The outlet arrangement had to accommodate the exhaust airflow as well as the acoustic treatment.

 

Gaps between the silencer system and the cooling towers were also included in the design. Damped acoustic panels at the base were proposed to close those untreated paths. Paying attention to the perimeter alone would have left an incomplete picture of how sound could escape.

 

Maintenance was considered at the same stage. Access openings and removable silencer splitters were incorporated into the proposal so that cleaning and inspection could be planned around the acoustic treatment.

 

The stated targets at the residential measurement position were no more than 58 dB(A) during the day and 48 dB(A) at night. The proposal also set requirements for ventilation, heat rejection and pressure loss. These are design targets and requirements. Achievement must be established through site measurements under agreed operating conditions.

 

The project illustrates why the receiver location matters. The towers defined the engineering constraints; the windows opposite defined where the acoustic outcome needed to be evaluated. Both informed the same design.